E44-503 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Water Cooler (Carbon Steel) · ★★
Water-side fouling drops K from 800 to 400W/m²K, outlet water temperature rise is insufficient, and equipment overheats.
[Mechanism] Calcium scale adheres to the wall, adding fouling resistance Rf.
[Calculation] Rf=0.5m²K/W gives K=1/(1/800+Rf)≈400, and Q=KAΔTm drops by half.
[Design Omission] No softening, no antiscalant, and no cleaning schedule were provided, leading to fouling.
1) Soften the inlet water (hardness ≤60mg/L as CaCO3) and add antiscalant to keep Rf<0.1, since wall calcium scale gives Rf=0.5, drops K from 800 to 400W/m²K, halves Q=KAΔTm, and leaves outlet water-temperature rise insufficient so equipment overheats; thus softening and scale inhibition suppress calcium scale, restore K, and protect outlet temperature;
2) Schedule chemical scale removal (acid cleaning quarterly; wash at Δp>0.08MPa), since scale thickens gradually and K drops before temperature rises become visible, thus removing scale on schedule to restore flow area;
3) Raise velocity to ≥1.5m/s to prevent settling, since calcium scale settles and adheres in low-velocity zones and hardens with time, thus raising velocity to cut residence time and suppress settling;
4) Provide online K monitoring (alarm on a 10% K drop), since fouling lowers K as the first symptom, ahead of overheating, thus alarming on K;
5) Alarm on outlet temperature (alarm if outlet temp < design lower limit), since a K drop leaves outlet temperature rise insufficient and risks equipment overheating, thus warning in advance;
6) Coat tube walls against fouling (non-stick / ceramic coating), since scale readily adheres to rough walls and a coating reduces adhesion, thus suppressing scale on coated walls;
7) Use side-stream filtration to cut suspended solids (side-stream flow 5-10% of circulation), since suspended particles act as scale nuclei and reducing the load suppresses scale, thus removing solids by side-stream filtration;
8) Write softening and scale removal into the water-cooler procedure, since the original design omitted softening and scheduled cleaning, the root cause of fouling, thus controlling by procedure.
GB/T 151-2014 Heat exchangers