E44-510 · Heat Exchanger Fouling and Insufficient Heat Transfer · Steam Heater Coil · ★★
Non-condensable gas buildup, K drop, slow heating, energy rise
[Mechanism] Non-condensable gases cling to the wall as a gas film.
[Calculation] The gas film cuts K by 40%, lowers heat-transfer Q, and slows warm-up.
[Design Omission] No non-condensable vent and no scheduled venting, so gas accumulates.
1) Install a non-condensable vent valve at the high point and vent on schedule (each shift / automatic); the wall gas film cuts K by 40%, lowers Q, slows warm-up and raises energy use, so venting breaks the film and restores K;
2) Slope the shell side toward the vent (route tubing to the vent); trapped gas stagnates, so a slope favors venting;
3) Monitor K (alarm when K drops 10%); non-condensable gas shows up first as a K drop, ahead of the energy rise, so K monitoring gives early warning;
4) Match the steam trap to prevent vapor binding (float / thermostatic traps); a vapor-bound trap traps gas, so proper trapping keeps venting effective;
5) Inspect vent valves on schedule (monthly actuation test); a blocked valve traps gas, so testing keeps it clear;
6) Maintain inlet steam dryness (steam separator); wet steam carries more non-condensables, so keeping steam dry reduces the gas load;
7) Monitor warm-up time (alarm on warm-up timeout); the gas film slows warm-up, so a timeout signals accumulation;
8) Write venting into the heater procedure; the original design omitted the non-condensable vent and scheduled venting, the root cause of gas buildup, so the procedure closes the loop.
GB/T 151-2014 Heat exchangers