E44-514 · Heat Exchanger Fouling and Insufficient Heat Transfer · Refrigerated Dryer Exchanger Plate · ★★
Cold plates ice up, air path blocked, dew point rises
[Mechanism] Evaporation temperature too low; condensed water freezes and seals the path.
[Calculation] Evaporation temp <0℃ freezes water, plugs holes, stops flow and raises dew point.
[Design Omission] No evaporation-temperature control and no drainage, so ice blocks the unit.
1) Hold evaporation temperature >2℃ to prevent plate icing; when evaporation temp <0℃, condensed water freezes, plugs holes, stops flow and raises dew point, so temperature control prevents ice and protects the air path;
2) Schedule condensate drainage (automatic trap); pooled water freezes in the cold zone, so scheduled drainage removes the source;
3) Pre-cool and dehumidify inlet air to cut moisture; humid air entering the cold plates freezes easily, so pre-cooling lowers humidity;
4) Fit a differential-pressure alarm (on Δp exceedance); ice blockage raises resistance and shows up as Δp, so the alarm prevents cutoff;
5) Bypass to prevent over-cooling (hot-gas bypass); over-cooling causes freezing, so bypass stabilizes temperature;
6) Limit flow to prevent rapid freezing; high airflow carries more water and freezes fast, so limiting flow cuts ice;
7) Schedule ice-melt inspection (shutdown hot flush); ice thickens and worsens blockage, so melting and inspecting restores flow;
8) Write temperature control and drainage into the dryer procedure; the original design omitted evaporation-temperature control and drainage, the root cause of ice, so the procedure closes the loop.
GB/T 151-2014 Heat exchangers