E44-518 · Heat Exchanger Fouling and Insufficient Heat Transfer · Marine Heat Exchanger Titanium · ★★
Marine growth adhesion, K drop, insufficient cooling
[Mechanism] Marine organisms cling to the titanium surface.
[Calculation] The fouling layer cuts K by 25%, raises outlet by 4℃, and leaves cooling insufficient.
[Design Omission] No chlorination and no flushing, so biofouling occurs.
1) Dose chlorine upstream of the filter to suppress marine growth; growth on the titanium (fouling layer K drop 25%, outlet +4℃, insufficient cooling), so chlorination suppresses adhesion and restores K;
2) Fit rotating brushes for online cleaning; biofouling thickens and hardens over time, so brushing keeps surfaces clean;
3) Outlet-temperature alarm (on +3℃ over limit); fouling causes insufficient cooling and temperature rise, so the alarm prevents efficiency loss;
4) Coat the titanium surface with antifouling coating; marine growth readily bonds to smooth surfaces, so the coating reduces adhesion and eases cleaning;
5) Raise flow velocity to prevent adhesion (≥1.5 m/s); organisms settle in low-velocity flow, so higher velocity suppresses attachment;
6) Schedule high-pressure flushing (periodic); once growth hardens it resists brushing, so high-pressure water removes it;
7) Rotate standby tubes (one in service, one standby); cleaning interrupts flow and operation, so rotation keeps service running;
8) Write chlorination and cleaning into marine practice; the original design omitted chlorination and cleaning, the root cause of biofouling, so the procedure closes the loop.
GB/T 151-2014 Heat exchangers