E44-520 · Heat Exchanger Fouling and Insufficient Heat Transfer · Heat Pump Evaporator Finned · ★★
Evaporator frosting, K drop, low suction pressure, poor heating
[Mechanism] Low temperature and high humidity cause frost on the fins.
[Calculation] The frost layer lowers α, cuts K by 30%, drops suction pressure by 0.1 MPa, and reduces heating.
[Design Omission] No defrosting and high humidity, so frosting occurs.
1) Schedule reverse-cycle defrosting to restore outside α; low temperature and high humidity cause frost on the fins (lower α, K drop 30%, suction −0.1 MPa), so reverse-cycle defrost melts frost and restores K;
2) Adjust the defrost interval by humidity (shorten in high humidity); humid conditions frost faster and need shorter intervals, so modulating the interval prevents thick frost;
3) Fit a suction-pressure alarm (below threshold); thick frost drops suction pressure as a symptom, so the alarm prevents poor heating;
4) Pre-heat and dehumidify inlet air; humid air passing over cold surfaces frosts easily, so pre-dehumidification cuts the frost source;
5) Widen fin spacing (≥4 mm); tight spacing lets frost bridge and block airflow, so wider gaps reduce bridging;
6) Modulate fan airflow to even out frost; uneven flow causes local thick frost, so even distribution reduces local buildup;
7) Drain meltwater freely (drain heater / heat trace); pooled water refreezes and plugs, so draining ice prevents blockage;
8) Write defrosting and drainage into the heat-pump procedure; the original design omitted defrosting and ice drainage, the root cause of frost, so the procedure closes the loop.
GB/T 151-2014 Heat exchangers