E44-522 · Heat Exchanger Fouling and Insufficient Heat Transfer · Oil-Station Cooler Water-Oil · ★★
Water-side fouling, K drop, high oil temperature, alarm
[Mechanism] Water-side fouling bonds to the wall and raises Rf.
[Calculation] Rf=0.4 cuts K by 40%, pushes oil temperature 12℃ over limit and triggers an alarm.
[Design Omission] No cleaning and no softening, so fouling occurs.
1) Clean and soften the water side to keep Rf<0.1; water fouling on the wall (Rf=0.4, K drop 40%, oil temp +12℃ over limit, alarm), so cleaning and softening lower Rf and restore K;
2) Schedule back-flushing (periodic reverse wash); fouling builds and hardens, so back-flushing removes it;
3) Oil-temperature alarm (on exceeding setpoint); scaling raises oil temperature with a safety risk, so the alarm prevents over-temperature;
4) Raise flow velocity to prevent settling (≥1.2 m/s); suspended solids settle in low-velocity zones, so higher velocity suppresses scaling;
5) Dose scale inhibitor; crystal nuclei bond to the wall and form scale, so inhibitor reduces deposition;
6) Use a side-stream filter to cut suspended solids; settled solids aid scaling, so side filtration reduces the load;
7) Inspect scale thickness on schedule (thickness gauge); scale thickens and temperature rises, so inspection guides cleaning;
8) Write cleaning and softening into the oil-station procedure; the original design omitted cleaning and softening, the root cause of fouling, so the procedure closes the loop.
GB/T 151-2014 Heat exchangers