E44-523 · Heat Exchanger Fouling and Insufficient Heat Transfer · Ammonia Cooler Shell-and-Tube · ★★
Ammonia-side oil film, K drop, evaporation-temperature rise, cooling-capacity loss
[Mechanism] Compressor oil enters with ammonia and bonds to the wall as a film.
[Calculation] The oil film Rf=0.5 cuts K by 45%, raises evaporation temperature by 3℃, and lowers cooling.
[Design Omission] No oil separator and no oil drain, so an oil film forms.
1) Add a high-efficiency oil separator and drain oil on schedule; compressor oil enters with ammonia and forms a wall film (Rf=0.5, K drop 45%, evaporation temp +3℃, cooling down), so separation and draining restore K;
2) Fit a low-point oil drain on the evaporator; oil is heavier than ammonia and settles at the bottom, so low-point draining reduces the film;
3) Fit an evaporation-temperature alarm (on +2℃ over limit); the oil film raises evaporation temperature and cuts capacity, so the alarm prevents loss;
4) Monitor oil-separator efficiency (outlet oil content); poor efficiency carries oil into the vessel, so monitoring prevents carryover;
5) Filter return gas to remove oil; oil circulates with return gas, so filtration cuts carryover;
6) Schedule oil-film washing (hot flush / solvent); once the film hardens it resists draining, so washing restores the surface;
7) Online K monitoring (alarm on 10% K drop); the oil film shows up first as a K drop, so monitoring gives early warning;
8) Write oil separation and draining into the ammonia-cooler procedure; the original design omitted separation and draining, the root cause of the oil film, so the procedure closes the loop.
GB/T 151-2014 Heat exchangers