MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Fluid Systems Error Case › Vacuum Pump Cooler Algae Blockage

Vacuum Pump Cooler Algae Blockage

E44-539 · Heat Exchanger Fouling and Insufficient Heat Exchange · Tubular Vacuum Pump Cooler · ★★

Problem Description

Algae in circulating water, reduced K, high pump temperature, reduced vacuum

Root Cause

[Mechanism] Algae adhere to the wall and block heat transfer.
[Calculation] An algae layer with Rf=0.3 lowers K by 30%, raises pump temperature, and reduces vacuum.
[Design Omission] No biocide treatment and no flushing, so algae blockage occurred.

Corrective Solution

1) Add biocide and algaecide treatment (residual chlorine 0.5-1.0mg/L) and flush; because algae adhere to walls, Rf=0.3 lowers K by 30%, raises pump temperature and reduces vacuum, treatment plus flushing removes algae and restores K;
2) Schedule backwashing (reverse wash weekly, intensified flush at Δp>0.08MPa); because algae build up and harden over time, periodic backwashing removes them;
3) Add a pump-temperature alarm (alarm at pump temperature > design +5℃); because algae blockage lowers K first as a pump-temperature rise and reduced vacuum, it gives early warning;
4) Raise flow velocity (≥1.2m/s) to prevent settling; because algae settle in low-velocity zones and grow under light, higher velocity reduces residence time and suppresses algae;
5) Shade against algae (cover cooling towers / water tanks to block light); because light promotes algae growth, shading suppresses it;
6) Add side-stream filtration (5-10% of circulating flow) to reduce biomass; because more biomass means more adhesion, cutting the load suppresses algae;
7) Inspect algae thickness on schedule (bi-monthly thickness measurement / visual); because algae thicken and worsen K loss and vacuum decline, quantifying it guides treatment;
8) Write biocide treatment and backwashing into the vacuum pump cooling procedure; because the original design omitted biocide and flushing, the root cause of algae blockage, the procedure closes the loop.

Checklist

Reference

GB/T 151-2014 Heat exchangers

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL