E44-545 · Heat Exchanger Fouling and Insufficient Heat Exchange · Tubular Thermal-Oil Heater Heat Exchanger · ★★
Oil overheating and coking, reduced K, high furnace temperature, higher energy use
[Mechanism] Excessive oil temperature causes coking on surfaces.
[Calculation] Excessive film temperature causes coking, Rf=0.5, K drops 45%, furnace temperature rises, and energy use climbs.
[Design Omission] Film temperature was not controlled and no oil change was done, so coking occurred.
1) Control film temperature (≤ oil thermal-cracking point, wall temperature ≤ allowable upper limit) to prevent coking, and change oil on schedule (every 2 years / when viscosity doubles); because excessive oil temperature causes coking, Rf=0.5 lowers K by 45%, raises furnace temperature and energy use, film-temperature control suppresses coking while oil changes restore K;
2) Test oil samples for viscosity (quarterly viscosity / acid number test); because viscosity rises before coke thickness accumulates and indicates cracking severity, viscosity testing gives early warning for oil change;
3) Add a furnace-temperature alarm (alarm at furnace temperature > design +10℃); because coking lowers K first as a furnace-temperature rise and higher energy use, it gives early warning;
4) Raise flow velocity (≥2.0m/s) to prevent stagnation; because low-velocity zones have long residence time and rising wall temperature that promotes coking, higher velocity reduces residence time and suppresses coking;
5) Use heat-resistant materials (316L / aluminized tubes); because ordinary materials have low temperature resistance and over-temperature causes oxide scaling that promotes coking, heat-resistant material extends life and suppresses coking;
6) Schedule decoking (mechanical / chemical decoking every 2 years); because cured coke adheres strongly and cleaning restores flow area, periodic decoking restores K;
7) Add inlet filtration (accuracy ≤25μm); because impurities promote coking and filtering them out cuts the coke source, filtration suppresses coking;
8) Write film-temperature control and oil changes into the thermal-oil heater procedure; because the original design omitted temperature control and oil changes, the root cause of coking, the procedure closes the loop.
GB/T 151-2014 Heat exchangers