E44-546 · Heat Exchanger Fouling and Insufficient Heat Exchange · Finned Spray Cooler · ★★
Wet hot air below dew point, fins gummed up, reduced air flow
[Mechanism] Wall temperature < dew point causes condensation and fin gumming.
[Calculation] Wall temperature < dew point causes condensation, α drops 40%, and air flow drops 25%.
[Design Omission] No insulation and no heat tracing, so gumming occurred.
1) Insulate the housing (insulation keeps wall temperature > wet-air dew point +5℃) to prevent condensation and gumming; because wall temperature below dew point makes condensate gum the fins, α drops 40% and air flow drops 25%, insulation raises wall temperature, prevents condensation and restores α;
2) Add inlet heat tracing (steam / electric tracing on the incoming air); because cold inlet air drives wall temperature below dew point and heat tracing raises temperature to prevent condensation, tracing provides anti-condensation protection;
3) Intensive ash removal (high-frequency rapping / compressed-air blowing); because gummed deposits adhere tightly and intensive cleaning restores ventilation, intensive cleaning removes the gum;
4) Add an air-flow alarm (alarm when air flow <75% of design); because gummed fins lower α first as reduced air flow, well before full blockage, it gives early warning;
5) Prevent material sticking (dehumidify inlet air / adjust moisture content); because wet material readily sticks to fins and lowering moisture reduces sticking, humidity adjustment prevents adhesion;
6) Monitor dew point (alarm when wall temperature < dew point); because the dew point rises before condensation and gumming, giving early warning, dew-point monitoring prevents condensation;
7) Schedule flushing to prevent buildup (high-pressure water flush of fins each shift); because material buildup worsens gumming and periodic flushing restores α, scheduled flushing suppresses buildup;
8) Write insulation and heat tracing into the spray cooler procedure; because the original design omitted insulation and heat tracing, the root cause of gumming, the procedure closes the loop.
GB/T 151-2014 Heat exchangers