E44-1064 · Heat Exchanger Fouling and Insufficient Heat Transfer · Heat Exchanger · ★★
Low flow velocity, fouling, efficiency drop
[Mechanism] The tube-side flow velocity in the heat exchanger is too low, causing deposition and fouling in stagnant zones and lowering K.
[Calculation] v=0.6 m/s (should be ≥1.0), stagnant-zone deposition, 2 mm fouling thickness after 6 months, K drops by 40%.
[Design Omission] No flow-velocity increase, no velocity verification, and no smaller tube diameter were provided.
1) Raise flow velocity to ≥1.0 m/s (upsize the pump or reduce tube diameter); because low v causes fouling and raising it slows fouling, this suppresses fouling;
2) Verify flow velocity≥ allowable lower limit (actual 0.6); because low velocity causes fouling and velocity verification preserves it, this suppresses fouling;
3) Switch to a smaller tube diameter (raise v to 1.2); because large tubes with low velocity cause fouling and changing diameter raises velocity, this suppresses fouling;
4) Add a scale inhibitor; because fouling reduces efficiency and inhibition slows it, this suppresses fouling;
5) Perform a heat-transfer test (measure K); because fouling was never verified and direct measurement confirms the velocity effect, this determines efficiency from data;
6) Install differential-pressure monitoring (fouling raises Δp); because fouling first shows up as rising resistance, this monitors fouling and gives early warning;
7) Stabilize flow velocity in operation (VFD maintains v); because load changes cause fouling and velocity control stabilizes it, this prevents fouling during operation;
8) Write velocity increase and verification into the calculation sheet; because the root cause of low-velocity fouling is the lack of velocity increase and verification, the calculation enforces control.
GB/T 151-2014 Heat exchangers