Knowledge Base › Fluid Systems Error Case › Parallel Pumps with Different Characteristics Fighting for Flow

Parallel Pumps with Different Characteristics Fighting for Flow

E44-079 · Uneven Flow Distribution · Parallel pump group · ★★

Problem Description

Two parallel pumps with different characteristics fight for flow, one pump exceeds its rated flow by 10% and cavitates at the inlet with a drop in head

Root Cause

[Flow Fighting] Different characteristic curves of the parallel pumps shift the operating point, so one pump exceeds its flow.
[Calculation] The characteristic difference deviates the flow split by 10% above the rated value, and the over-flowing pump cavitates.
[Design Omission] Neither the same model and characteristic nor flow balancing was provided, so the pumps fight for flow and cavitate.

Corrective Solution

1) Select pumps of the same model and characteristic for parallel operation, because different characteristic curves shift the operating point and cause flow fighting, while identical characteristics synchronize them, thereby preventing one pump from over-flowing;
2) Fit a balancing valve at each pump outlet to adjust the flow, because the valve splits the flow by design and evens it between the two pumps, thereby eliminating the flow fighting;
3) Control the variable-frequency drives at the same speed, because a speed difference causes a characteristic difference and synchronization gives the same operating point, thereby steadying the split;
4) Provide flow monitoring (an independent meter on each pump), because the flow fighting must be quantified and monitoring reveals it early, thereby enabling timely action;
5) Verify the parallel operating point (intersection of the combined curves), because a shifted operating point causes over-flow and verification predicts it, thereby enforcing design control;
6) Provide cavitation monitoring at the inlet (NPSHa margin), because the over-flowing pump cavitates and monitoring gives early warning, thereby protecting the impeller from damage;
7) Measure the flow balance at commissioning (deviation ≤5%), because balance is the goal of parallel operation and must be measured, thereby performing acceptance;
8) Build the parallel-pump design into the pump-house standard, because the original selection of mismatched characteristics caused the flow fighting, thereby controlling it at the selection stage.

Checklist

Reference

GB/T 13006-2013 Centrifugal pumps — Efficiency