E44-773 · Uneven Flow Distribution · Thermometer Well · ★★
Insertion depth disturbed the flow, measurement off >2℃, local separation
[Mechanism] The insertion depth or counter-flow insertion disturbs the flow.
[Calculation] An insertion depth over one third of the pipe diameter distorts the local velocity and biases the measurement >2℃.
[Design Omission] The position was not defined and the insertion was not kept shallow, so it was wrong.
1) Define a shallow insertion position (insertion depth ≤ one third of the pipe diameter, oblique insertion downstream), because the original depth over one third of the pipe diameter distorted the local velocity, biased the measurement >2℃, and disturbed the downstream distribution, thereby reducing the disturbance by shallow insertion;
2) Choose downstream insertion (sensing tip facing downstream to reduce swirl), because counter-flow insertion disturbs the flow and downstream insertion steadies it, thereby reducing swirl;
3) Verify the straight run of the measurement section (upstream and downstream runs ≥10D), because a short run leaves the flow unsettled and biases the measurement, thereby restoring accuracy;
4) Limit the insertion depth (add a stop sleeve to prevent over-insertion), because deep insertion disturbs the flow and a limit prevents it, thereby steadying the flow;
5) Check the flow regime (observe the flow or measure the deviation downstream of the well), because gradual disturbance widens the deviation and early detection helps, thereby checking the flow;
6) Run a flow test (trace the flow field downstream of the well), because the omitted test let the disturbance go unnoticed, thereby proving a steady flow;
7) Control the total pressure (keep the total flow steady against amplified disturbance), because off-design conditions worsen the disturbance and stabilization soothes it, thereby stabilizing the pressure;
8) Write the position definition and shallow insertion into the assembly card, because the undefined position was the root cause and the assembly card enforces it, leaving the flow undisturbed.
GB/T 2624.1-2006 Flow measurement