E44-081 · Level Control Failure · Make-Up Water Tank Float Valve · ★★
The float valve stuck and would not close fully, so the tank overflowed continuously, raising water consumption and flooding the floor, several overflows a month
[Sticking] Scale on the guide rod or a deformed float jams the valve stem, so it cannot close fully.
[Calculation] The sticking leaves a gap at the valve port that overflows continuously, so the level exceeds the setpoint.
[Design Omission] No overflow collection was provided and the guide rod was not cleaned periodically, so the sticking caused overflow.
1) Clean the guide rod to remove scale and keep it free, because scale on the guide rod or a deformed float jams the valve stem and cleaning frees it, thereby closing fully without overflow;
2) Change to a sticking-resistant float structure (e.g., piston type or ball-guided), because the new structure tolerates more scale and sticks less, thereby going long periods without overflow;
3) Provide overflow collection and alarm, because any overflow can then be collected and alarmed instead of flooding the floor, thereby protecting the environment and giving early warning;
4) Provide a dual float or a backup motorized valve, because if a single valve sticks the backup takes over, so make-up is neither interrupted nor overflowing, thereby improving reliability;
5) Interlock a high level to stop make-up (cut the pump at the upper limit), because the interlock stops overflow at the source without relying on the valve closing fully, thereby adding a second safeguard;
6) Maintain the guide rod regularly (monthly lubrication), because sticking is gradual and regular maintenance prevents it, thereby keeping it free;
7) Prove on trial run that no overflow occurs (run at full water), because overflow is the outcome and the trial run provides the measurement, thereby accepting the installation;
8) Include sticking prevention in the tank design, because the omitted prevention caused the overflow and the design stage should select a sticking-resistant structure.
GB/T 50015-2019 Code for Design of Building Water Supply and Drainage