E44-083 · Level Control Failure · Compressed-Air Agitated Tank · ★★
Tank-top air pressure fluctuation was not compensated, so the DP level reading differed from the truth by 0.5m, making the metering inaccurate and the batching wrong
[Air-Pressure Interference] The fluctuating tank-top air pressure changes the pressure on the vapor side of the DP transmitter, biasing the reading.
[Calculation] An air-pressure fluctuation of 0.5m water column biases the reading by 0.5m.
[Design Omission] No vapor-phase impulse compensation was provided and the air pressure was not stabilized, so the reading was inaccurate.
1) Provide a vapor-phase pressure-compensating impulse line (route the vapor side in parallel to the transmitter), because the fluctuating tank-top air pressure changes the vapor-side pressure and compensation cancels it, thereby letting the reading reflect the true liquid column;
2) Stabilize the tank-top air pressure (buffer tank or pressure regulation), because a 0.5m-water-column pressure fluctuation directly biases the reading and stabilizing it makes the reading accurate, thereby removing the bias at the source;
3) Equalize both impulse lines (vapor and liquid sides in parallel), because both sides are affected by the air pressure in step and the differential pressure stays unchanged, thereby steadying the reading;
4) Calibrate periodically (compare with the gauge glass), because sensor drift biases the reading and calibration corrects it, thereby maintaining accuracy;
5) Compare the remote reading with the field reading, because an inaccurate remote reading causes wrong batching and comparison verifies it, thereby confirming the reading;
6) Provide air-pressure monitoring, because the pressure fluctuation is the interference source and monitoring gives warning, thereby stabilizing it in time;
7) Prove on trial run that the reading is accurate (within 0.05m of the measured level), because inaccurate metering causes wrong batching and the trial run provides the measurement, thereby accepting the installation;
8) Include compensation in the instrument design, because the omitted compensation biases the reading and the vapor-phase impulse line should be laid out at the design stage.
HG/T 21581-2010 Instrument installation drawings