E44-133 · Level Control Failure · Dual-Flange Transmitter on Tank · ★★
Insufficient fill oil in the capillary drifted the zero by 0.25m and displayed a false level, causing feed overfill
[Insufficient Fill Oil] An air gap in the capillary makes the transfer sluggish and offsets the zero.
[Drift] The air gap deforms under pressure, drifting the zero by 0.25m with temperature.
[Design Omission] Air was not fully vented and the zero was not calibrated periodically, so the false level caused overfill.
1) Fill the oil, vent the air from the capillary, and seal it, because the air gap makes the transfer sluggish and offsets the zero and venting keeps it accurate, thereby venting the air to keep it accurate;
2) Provide periodic zero calibration of the dual-flange transmitter (≤±0.05m), because a 0.25m drift causes a false level and periodic calibration corrects it, thereby calibrating on schedule;
3) Build temperature compensation into the transmitter migration, because the temperature drift is large and compensation reduces it, thereby reducing the drift;
4) Compare the remote reading with a local dual meter, because a single meter drifts unnoticed and the two meters cross-check each other, thereby cross-checking;
5) Interlock a high level to stop feed and prevent overfill, because a false high causes overfill and the interlock protects it hard, thereby protecting hard;
6) Fix the capillary against mechanical stress, because bending and squeezing the oil offsets the reading and fixing steadies it, thereby steadying the reading;
7) Prove on trial run that the zero drift is ≤±0.05m, because the design requires measurement and the trial run confirms it, thereby confirming delivery;
8) Include oil filling and air venting in the installation procedure, because the omitted venting was the root cause of the drift and the procedure must constrain it.
GB/T 17614.1-2008 Transmitters for use in industrial-process control systems