E44-134 · Level Control Failure · DP Level Transmitter on Steam Separator · ★★
The vapor-phase impulse line had no balance container, so intermittent condensate made the reading fluctuate ±0.4m and read a false low
[Intermittent Condensation] Evaporation of the condensate on the vapor side changes the reference pressure, so the reading drifts.
[Inaccuracy] Without a balance container the liquid columns on the two sides are unequal.
[Design Omission] No balance container was provided and no negative migration was set, so the reading was inaccurate.
1) Provide a balance container on the vapor-phase impulse line to keep the condensate constant, because intermittent condensation changes the reference pressure and drifts the reading, while a constant column steadies it, thereby steadying the reading;
2) Set the negative migration amount from the balance container, because a wrong migration offsets the reading and an accurate calculation corrects it, thereby setting the migration correctly;
3) Make the two impulse lines of equal bore, equal length, and the same temperature, because a temperature difference causes a density difference and symmetry reduces it, thereby reducing the difference;
4) Flush the impulse lines at intervals against plugging, because plugging loses the pressure and fakes the reading and periodic flushing clears it, thereby flushing periodically;
5) Compare the reading with a local dual meter, because a single meter drifts easily and cross-checking exposes a false reading, thereby identifying false readings;
6) Apply temperature compensation to the remote level, because temperature changes the density and compensation keeps it accurate, thereby compensating accurately;
7) Prove on trial run that the reading fluctuation is ≤±0.1m, because the design requires measurement and the trial run confirms it, thereby confirming delivery;
8) Include the negative-migration calculation in the level design, because the omission was the root cause of the inaccuracy and the design must include it.
HG/T 21581-2010 Instrument installation drawings — Level