Knowledge Base › Fluid Systems Error Case › Media Adhesion on Float Level Switch Causing False Actuation and Frequent Start-Stop

Media Adhesion on Float Level Switch Causing False Actuation and Frequent Start-Stop

E44-135 · Level Control Failure · Float Switch in Sewage Tank · ★★

Problem Description

Adhesion on the float held the switch at high level, so the pump ran dry and started-stopped frequently, 20 times a month, burning out one motor

Root Cause

[Adhesion] Dirt adhering to the float reduces buoyancy and jams the position.
[False Actuation] Jamming at high level keeps the pump running or running dry.
[Design Omission] No anti-adhesion float was selected and no dead band was provided, so false actuation was frequent.

Corrective Solution

1) Select an anti-adhesion float (coated or high-buoyancy), because dirt adhering to the float jams the position and an anti-adhesion float keeps the switching reliable;
2) Provide a start-stop dead band against frequent actuation, because without a dead band the 20 starts-stops a month damage the motor and the dead band suppresses the frequency;
3) Flush the float guide rod at intervals to clear adhesion, because adhesion builds up gradually and cleaning restores reliable switching, thereby flushing periodically;
4) Provide redundant dual-float switching for comparison, because a single jammed float is hard to detect and the two floats cross-check each other;
5) Provide dry-run protection to stop the pump and prevent motor burnout, because dry running burned out one motor and the protection stops it;
6) Add a cable weight as a counterweight against tangling, because tangling jams the switch and the counterweight keeps it straight;
7) Prove on trial run that the start-stop frequency is ≤ the design value, because the design requires measurement and the trial run confirms it, thereby confirming delivery;
8) Include anti-adhesion cleaning in operation and maintenance, because the omitted cleaning was the root cause of the adhesion and O&M must include it.

Checklist

Reference

GB/T 20819-2018 Process control — System evaluation