Knowledge Base › Fluid Systems Error Case › Foam Interference on Agitated-Tank Level Gauge Causing a False High

Foam Interference on Agitated-Tank Level Gauge Causing a False High

E44-183 · Level Control Failure · Radar Gauge on Agitated Reactor · ★★

Problem Description

Agitation foam made the radar level gauge read a false high of 0.4m, causing tank overflow and product loss

Root Cause

[Foam] Foam makes the radar measure falsely high.
[False High] The foam interface is misjudged as a high level.
[Design Omission] No foam suppression or dual metering was provided, so a false high resulted.

Corrective Solution

1) Provide a foam-suppression algorithm or an air-purge method on the radar level gauge, because agitation foam caused a false high of 0.4m and tank overflow, thereby suppressing the foam and measuring accurately;
2) Provide dual metering (radar + weighing) for cross-checking, because a single meter is affected by foam and the two meters verify each other, thereby cross-checking;
3) Lower the agitation speed to reduce foaming, because fast agitation makes more foam and speed control reduces it, thereby reducing foam;
4) Provide a defoaming spray on the tank top, because foam is hard to break and spraying breaks it, thereby defoaming;
5) Interlock a high level to stop feed, because the false high causes overflow and the interlock protects it hard, thereby protecting the tank;
6) Clean and verify the foam at intervals, because foam conditions change and periodic calibration keeps it right, thereby calibrating periodically;
7) Prove on trial run that the level reading is the true value with no false high, because the design requires measurement and the trial run confirms it, thereby confirming delivery;
8) Include foam suppression in the level design, because the omitted suppression was the root cause of the false high and the design must include it.

Checklist

Reference

HG/T 21550-2013 Magnetic flap level gauges

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL