E44-184 · Level Control Failure · Outdoor Tank Level Impulse Line · ★★
An outdoor impulse line froze shut, showing a false low and causing overfilling and overflow
[Freeze Blockage] The impulse line froze, cutting off the pressure transfer.
[False Low] The interrupted transfer reads low and causes overfilling.
[Design Omission] No insulation or heat tracing and no freeze protection were provided, so the line plugged.
1) Insulate and heat-trace the outdoor impulse line against freeze blockage, because freeze blockage reads a false low and causes overfilling and overflow, while tracing keeps it open, thereby keeping the line clear;
2) Slope the impulse line for drainage against liquid accumulation and freezing, because accumulated liquid freezes and sloping drains it, thereby keeping it flowing;
3) Provide self-regulating electric heat tracing, because low temperature freezes the line and temperature control prevents it, thereby controlling the temperature;
4) Provide a low-point drain against ice, because ice plugs the line and draining clears it, thereby draining the line;
5) Compare two meters to detect a false low, because a single frozen meter is hard to detect and dual comparison verifies it, thereby providing cross-checking;
6) Prove the line clear at intervals against plugging, because it freezes gradually and periodic proving clears it, thereby ensuring periodic clearing;
7) Prove on trial run at low temperature that no false low occurs, because the design requires measurement and the trial run confirms it, thereby confirming delivery;
8) Include freeze protection in the outdoor level design, because the omitted protection was the root cause of the freeze blockage and the design must include it.
HG/T 21581-2010 Instrument installation drawings — Level