Knowledge Base › Fluid Systems Error Case › Broken Magnetostrictive Probe Rod

Broken Magnetostrictive Probe Rod

E44-617 · Level Control Failure · Magnetostrictive · ★★

Problem Description

Broken rod, loss of indication

Root Cause

[Mechanism] A broken rod loses the measurement.
[Calculation] The break loses the indication.
[Design Omission] No rod guard was provided, the travel was not limited, and it was not inspected, so the rod broke.

Corrective Solution

1) Add a guard tube against breaking (stainless guard tube Φ12, wall 1.5mm, enclosing the probe rod), because the original magnetostrictive rod (Φ8) broke from a hard float impact or a knock by a cleaning tool and a break loses the whole span, while the guard takes the mechanical impact, thereby protecting the rod and keeping the reading continuous;
2) Limit the float travel (upper stop ring ≥50mm from the rod top), because the float overrun strikes the rod end and breaks it and the stop limits it, thereby preventing impact breakage;
3) Change to a flexible float connection (flexible coupling between float and guide rod, ±5° of float allowed), because a rigid connection transmits lateral force and bends the rod while a flexible one relieves the offset, thereby reducing the bending moment;
4) Calibrate zero and full (calibrate on commissioning, error ≤0.1%FS), because a break or a weak signal loses the reading and calibration verifies it, thereby confirming the datum;
5) Control media corrosion (change the rod to 316L, chloride-resistant), because corrosion thins the rod until it breaks and corrosion resistance keeps the section, thereby extending service life;
6) Check the rod condition (look for bending or cracks monthly), because gradual failure loses the reading and inspection catches it early, thereby allowing preemptive replacement;
7) Choose a corrosion-resistant rod (Hastelloy C276 for highly corrosive media), because corrosion breaks the rod and corrosion resistance keeps it sound, thereby preventing breakage;
8) Write the rod guard and travel limit into the specification, because the omitted rod guard was the root cause of the breakage and freezing them into the specification enforces design review.

Checklist

Reference

GB/T 25922-2010 Level meters

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »