E44-618 · Level Control Failure · Capacitance Level Transmitter · ★★
Material build-up, reading deviation
[Mechanism] Material build-up shifts the capacitance.
[Calculation] The build-up causes the deviation.
[Design Omission] The probe type was not selected properly, the probe was not cleaned, and no compensation was provided, so material built up.
1) Choose an insulated anti-stick probe (PTFE lining, surface energy <18mN/m), because the original bare stainless probe picked up slurry build-up (0.5mm thick, dielectric constant εr=8), which raised the equivalent capacitance and inflated the reading by 0.3m, while non-stick PTFE keeps material off, so the capacitance reflects only the true liquid column and the reading returns to true;
2) Clean the probe at intervals to remove build-up (high-pressure water wash every shift until the build-up is gone), because gradual thickening increases the false reading and cleaning restores it, thereby maintaining accuracy;
3) Provide build-up compensation (software zero shift to offset the constant build-up capacitance), because constant build-up can be measured and compensated and the reading is true after the shift, thereby reducing the false high;
4) Improve the probe finish (polish to Ra0.4μm), because a rough surface holds build-up and a smooth one reduces adhesion, thereby lowering build-up;
5) Control media viscosity (add thinner to keep viscosity <500cP), because sticky media build up and controlling viscosity reduces adhesion, thereby preventing build-up;
6) Calibrate empty and full (calibrate with the tank empty or full, error ≤0.5%), because build-up causes deviation and calibration corrects it, thereby confirming accuracy;
7) Check the deviation at intervals (log the false-high trend), because gradual build-up increases the deviation and inspection catches it early, thereby allowing timely cleaning;
8) Write the anti-stick selection and compensation into the specification (for build-up media, no bare probes — use PTFE), because the omitted anti-stick selection was the root cause and freezing it into the specification enforces design review.
GB/T 25922-2010 Level meters