E44-648 · Level Control Failure · Temperature compensation · ★★
No compensation, reading offset
[Mechanism] Without temperature compensation the density is off.
[Calculation] The missing compensation causes the offset.
[Design Omission] No temperature measurement, no compensation and no checks were provided — so the compensation was missed.
1) Add temperature measurement points to correct the density (a PT100 on each tank, corrected by ρ(T)): because the original lack of temperature compensation let the medium density change with temperature (Δρ=2%/10℃) and offset the differential-pressure reading (0.1m off), measuring the temperature and correcting the density fixes it so the reading returns to the true value;
2) Build a temperature-density curve (a ρ-T table loaded into the device): because changing conditions offset the reading and the curve compensates it, the reading is steady;
3) Select an instrument with temperature compensation (built-in density compensation): because cold offsets it and temperature compensation corrects it, it is steady;
4) Verify the temperature point (calibrate the PT100, error ≤0.5℃): because an offset miscompensates and calibrating the temperature fixes it, the compensation is correct;
5) Control the temperature against variation (insulation holding ΔT <5℃): because changing conditions offset it and temperature control steadies it, the compensation demand drops;
6) Check the offset (compare daily): because gradual drift misleads and checking gives early warning, compensation is timely;
7) Periodically check the compensation calculation (verify the curve monthly): because drift develops and verification corrects it, the compensation is accurate;
8) Write the temperature measurement and density correction into the specification: the original lack of compensation was the root cause of the offset, so the spec locks it in and specification governs it.
GB/T 17614.1-2008 Transmitters for use in industrial-process control systems