E44-086 · Piping Supports and Thermal Expansion · Large-bore water pipe hanger · ★★
Insufficient hanger capacity sags the pipe, reversing the slope so drainage is poor and sediment blocks it
[Sag] An undersized hanger selection makes the deflection exceed the limit and alters the pipe slope.
[Calculation] A large hanger spacing lets the load sag the pipe beyond the allowable deflection, reversing the slope.
[Design Omission] The hanger was not selected by load and the spacing was large — causing sag and sediment buildup.
1) Select the hanger size by load (compute the spacing and the load): because an undersized hanger exceeds the deflection limit and sizing by load carries it, the pipe does not sag;
2) Reduce the hanger spacing (increase the hanger density): because a large spacing raises the deflection and the load and reducing it lowers them, the slope is maintained;
3) Add a saddle to share the load: because the saddle carries weight and cuts the hanger load, the double support is stable and sag is prevented;
4) Verify the deflection to hold the slope (deflection < the slope allowance): because sag reverses the slope and verifying the deflection preserves the drainage slope, no sediment accumulates;
5) Recheck the drainage slope direction (ensure i≥ the design value): because a reversed slope clogs and the recheck confirms the right direction, drainage is free;
6) Check the sag periodically (visual / laser measurement): because sag is progressive and regular checking prevents it, the slope is maintained;
7) Measure the slope direction at trial run (flow water and watch the direction): because sediment buildup is the result and measuring the slope verifies it, acceptance follows;
8) Make the hanger a mandatory item in the support design: the original failure to size the hanger by load caused the sag, so the load is calculated at the design stage.
GB/T 20801-2020 Pressure piping code