MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Fluid Systems Error Case › Thermal Displacement Offset Not Considered

Thermal Displacement Offset Not Considered

E44-792 · Piping Supports and Thermal Expansion · Thermal Displacement · ★★

Problem Description

No pre-offset, displacement offset >5mm, rub and jamming

Root Cause

[Mechanism] Without calculating the thermal-displacement direction, the pre-offset is missing.
[Calculation] Without pre-offset the hot-state displacement offsets >5mm and rubs and jams against the adjacent parts.
[Design Omission] The displacement was neither calculated nor pre-offset — so it must be calculated.

Corrective Solution

1) Calculate the thermal displacement and pre-offset it (pre-offset by the displacement vector and reserve an allowance): because the original lack of pre-offset drove the hot-state displacement off >5mm and rubbed and jammed it against the adjacent parts, the pre-offset is reserved;
2) Check the displacement direction (verify the displacement vector at each point): because an error rubs and the check corrects it, the direction is checked;
3) Leave a pre-offset amount (pre-offset in the opposite direction in the cold state): because without it jamming occurs and the allowance keeps it free, the allowance is left;
4) Provide guides to limit the offset (guide supports keep it coaxial): because offset jams and guides correct it, guides are provided;
5) Monitor the offset condition (displacement-mark monitoring, alarm at offset >3mm): because a progressive offset worsens the rub and early awareness helps, the offset is monitored;
6) Perform a hot test (raise the temperature, record the actual displacement and compare with the calculation): because the original lack of testing left the offset undiscovered, the test reveals the true displacement, so the hot test is run;
7) Control the temperature ramp rate (≤30℃/h): because a rapid change offsets and a slow one keeps it under control, the ramp rate is controlled;
8) Write the pre-offset and direction check into the assembly card: the original design omission was the root cause of the offset, so assembly controls the work and no rub or jamming occurs.

Checklist

Reference

GB/T 20801.3-2020 Design code for industrial metallic piping

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL