E44-832 · Piping Supports and Thermal Expansion · Support Elevation · ★★
Wrong support elevation, pipe sag / misalignment, stress
[Mechanism] A wrong support elevation makes the pipe sag and misalign under bending.
[Calculation] An elevation error >10mm raises the deflection / bending stress.
[Design Omission] The elevation was neither measured nor checked — so it must be measured.
1) Measure the elevation and readjust (survey with a level and set the top height per drawing): because the original elevation error >10mm made the pipe sag and misalign under bending and raised the stress, it is measured and readjusted to level;
2) Check the support top height (top-height deviation ≤3mm): because a difference causes sag and the check corrects it, the height is checked;
3) Set a datum line (run a datum line to unify the elevations): because guesswork leads to error and a datum ensures accuracy, the datum is set;
4) Monitor the sag condition (level / laser measurement, alarm at deviation >5mm): because progressive sag increases bending and early awareness helps, the sag is monitored;
5) Perform a load test (hydrostatic test to check the elevation / deflection): because the original lack of testing left the misalignment undiscovered, the test confirms compliance, so the load test is run;
6) Control assembly accuracy (assemble and align per drawing): because an error causes sag and control corrects it, assembly is controlled;
7) Carry out periodic elevation checks (re-survey every quarter): because progressive error increases bending and periodic checks prevent it, the elevation is checked;
8) Write the measurement, readjustment and datum into the assembly card: the original lack of measurement was the root cause of the elevation issue, so assembly controls the work and the elevation is correct.
GB/T 17116.1-2018 Pipe supports and hangers