E44-037 · Throttling Noise and Vibration · Feedwater Control Valve · ★★
A high pressure-drop ratio causes cavitation noise of 95dB(A) downstream and cracks the valve body, with two valves replaced per month
[Cavitation] Δp/p1>0.5 flashes the fluid downstream; the bubble-collapse noise ∝ Δp².
[Vibration] The cavitation impact force resonates and fatigues the valve stem.
[Design Omission] No staged pressure reduction and no cavitation-resistant trim — the cavitation noise caused cracking.
1) Use a multi-stage reducing trim to split the pressure drop: because a single stage with Δp/p1>0.5 flashes and cavitates downstream and the noise ∝ Δp², several stages each keep the ratio <0.5;
2) Select a cavitation-resistant labyrinth or cage valve: because the labyrinth throttles in stages and resists cavitation, the valve type resists erosion;
3) Limit the single-stage pressure-drop ratio to ≤0.5: because a ratio above 0.5 always flashes, the ratio is limited to prevent erosion;
4) Provide a buffer downstream to reduce flashing: because the buffer stabilizes the flow and reduces bubble collapse, erosion and noise decrease;
5) Add damped supports to the valve body to suppress vibration: because the cavitation impact resonates and fatigues the stem, damping absorbs the energy;
6) Add a sound hood where noise exceeds 85dB: because 95 exceeds the environmental limit, insulation meets the target;
7) Measure noise ≤85dB(A) at commissioning (originally 95): because meeting the noise target means no cavitation, acceptance is granted;
8) Include the pressure-reduction design in control-valve selection: the original lack of staged reduction was the root cause of cavitation, so it must be included in selection.
GB/T 17213.1-2015 Industrial-process control valves