E44-191 · Throttling Noise and Vibration · Fan outlet diffuser · ★★
An excessive outlet diffuser angle generated 85dB vortex noise and shell vibration
[Vortex noise] A large diffuser angle produces separated vortices.
[Vibration] Vortex pulsation excites shell vibration.
[Design Omission] No diffuser-angle control, no silencing, hence the noise.
1) Control the fan outlet diffuser angle to ≤15° to prevent vortex separation, since the large angle produced 85dB vortex noise and vibration, thus controlling the angle steadies the flow;
2) Fit a silencer at the outlet, since vortex pulsation makes noise, thus silencing;
3) Stiffen the shell with ribs to raise rigidity and suppress vibration, since vortices excite shell vibration, thus adding ribs;
4) Provide enough straight outlet duct to steady the flow, since a short run is disturbed, thus lengthening the straight run;
5) Control the clearance between the impeller and the shell, since a large clearance makes vortices, thus controlling the clearance;
6) Use vibration-damping pads at the base, since vibration transmits, thus damping vibration;
7) Run-in test the noise to ≤85dB with no vibration, since the design requires measurement, thus confirming at delivery;
8) Include the diffuser angle and silencing in the fan outlet, since the original omission is the root cause of the vortex noise, thus the design must include it.
GB/T 50275-2010 Fan, Compressor and Pump Installation Code