E44-841 · Throttling Noise and Vibration · Control valve · ★★
A DN100 control valve with 4.0MPa upstream and 0.4MPa downstream, a pressure-drop ratio of 0.1, had 98dB(A) outlet noise, exceeding the GB/T17213 limit of 85dB(A)
[Mechanism] High-pressure gas reaches sonic velocity after the vena contracta at the trim; turbulence and shock waves radiate broadband noise; when the pressure-drop ratio x=p2/p1<0.5, choked flow sets in and the noise surges.
[Calculation] Δp=3.6MPa, x=0.4/4.0=0.1<0.5 enters choked flow; the sound power level Lw≈112dB and the measured outlet is 98dB(A).
[Design Omission] No staged pressure reduction, no downstream silencer, no choked-flow noise check.
1) Stage the pressure reduction (two valves in series, each dropping 1.8MPa, raising the single-stage x to 0.5), since the original single valve with Δp3.6MPa entered choked flow at 112dB, so staging keeps x>0.5 and cuts the noise;
2) Verify the sound level (≤85dB(A) with a silencer at the outlet), since exceeding 85dB(A) disturbs and verification meets it, thus verifying sound;
3) Add a downstream silencer (resistive, insertion loss ≥15dB), since the bare pipe radiated 98dB(A) and silencing lowers it, thus silencing;
4) Raise the downstream backpressure (a surge tank after the valve keeps p2≥0.5p1), since low backpressure causes choked flow and raising it leaves the choked regime, thus raising pressure;
5) Inspect the noise (a handheld sound-level meter at the outlet, alarm >85dB(A)), since gradual wear raises the noise and early detection catches it, thus inspecting noise;
6) Run a sound power test (measure Lw per GB/T3767), since the lack of testing left the noise undetected and the test reveals the true level, thus sound testing;
7) Control the opening and avoid small openings (working opening ≥30%), since a small opening concentrates the velocity and raises the noise and controlling it stabilizes, thus controlling the opening;
8) Write the staged pressure reduction and silencing into the specification, since the original omission is the root cause of the noise and locking it in closes the loop, thus controlling it in the spec.
GB/T 17213.1-2015 Industrial-process control valves