E44-845 · Throttling Noise and Vibration · Angle valve · ★★
A DN50 angle valve with 2.5MPa nitrogen inlet and 0.3MPa outlet had an outlet velocity of 41m/s and jet noise of 95dB(A)
[Mechanism] After the right-angle turn in the angle valve, the high-speed jet strikes the pipe wall, forming strong turbulent jet noise.
[Calculation] Outlet v=Q/A=0.08/0.00196=40.8m/s, Mach number Ma=0.12; the jet noise Lw∝(v/c)⁸ grows as the eighth power of the velocity.
[Design Omission] No bore enlargement to cut the speed, no silencer, and the outlet straight pipe is too short.
1) Enlarge the outlet to cut the speed (outlet pipe from DN50 to DN80, v from 41 down to 16m/s), since the original 41m/s jet gave 95dB(A), thus enlarging the outlet cuts the speed;
2) Verify the outlet velocity (v≤30m/s or Ma≤0.3), since exceeding it makes noise and verification controls it, thus verifying velocity;
3) Add a silencer (resistive, insertion loss ≥15dB), since the bare pipe radiates 95dB(A) and silencing lowers it, thus silencing;
4) Lengthen the straight pipe (outlet ≥10D for gradual expansion), since short impacts the wall and long diffuses, thus lengthening;
5) Monitor the noise (sound-level meter at the outlet, alarm >85dB(A)), since gradual growth approaches the limit and early detection catches it, thus monitoring noise;
6) Run an acoustic test (measure Lw per GB/T3767), since the lack of testing left the noise undetected and the test reveals the level, thus testing sound;
7) Control the opening to avoid vibration (operate ≥25%), since small concentrates the jet and control steadies it, thus controlling the opening;
8) Write the flaring and silencing into the specification, since the original lack of flaring is the root cause of noise and locking it in closes the loop, thus controlling it in the spec.
GB/T 3767-2016 Determination of sound power levels of noise sources using sound pressure