E44-873 · Throttling Noise and Vibration · Throttling valve · ★★★
Quick closing of the throttling valve produced a water hammer pressure wave of ±0.8MPa, with pipe vibration and noise
[Mechanism] Quickly closing the throttling valve changes the velocity abruptly; the sudden momentum change generates a water hammer pressure wave that strikes the pipe wall and radiates sound.
[Calculation] Water hammer Δp=ρcΔv=1000×1200×0.7=0.84MPa strikes the piping system.
[Design Omission] No slow closure, no closure-speed verification, no buffer.
1) Close slowly to prevent water hammer (valve closing time ≥30s), since the original quick closure at Δp0.84MPa gave water hammer noise, thus slow closure reduces the hammer;
2) Verify the closure rate (rate of change ≤0.1m/s), since too fast hammers and verification slows it, thus checking the rate;
3) Add a buffer tank (outlet buffer cuts the pressure wave), since a sudden change hammers and the tank cuts it, thus buffering;
4) Replace with a slow-closing valve (slow-closing throttling valve), since a hard closure causes hammer and the replacement is gentle, thus replacing the valve;
5) Monitor the hammer (measure the pressure wave, alarm >0.5MPa), since gradual hammering approaches cracking and early detection catches it, thus monitoring the hammer;
6) Run a hammer test (quick close and measure Δp), since the lack of testing left the hammer undetected and the test reveals the wave amplitude, thus testing the hammer;
7) Control the flow to steady the speed (limit the rate), since changing conditions cause hammer and control steadies it, thus controlling speed;
8) Write the slow closure and speed verification into the specification, since the original lack of slow closure is the root cause of hammer and locking it in closes the loop, thus controlling it in the spec.
GB/T 20801.3-2020 Design code for industrial metallic piping