E44-874 · Throttling Noise and Vibration · Pressure-reducing station · ★★★
A three-stage pressure-reducing station put out 91dB(A), exceeding the plant boundary
[Mechanism] The pressure-reducing station concentrates the pressure drop in multi-stage throttling, and the high-speed jets radiate strong noise.
[Calculation] Total Δp=2.5MPa; with no silencing at any stage, the outlet reaches 91dB(A), exceeding the 85dB(A) plant boundary.
[Design Omission] No staged noise reduction, no station silencing, no sound verification.
1) Reduce the pressure in stages to cut noise (each stage x>0.5), since the original total Δp2.5MPa concentrated gave 91dB(A), thus staging cuts the noise;
2) Verify the sound level (station boundary ≤85dB(A)), since exceeding it violates limits and verification meets them, thus verifying sound;
3) Add station silencing (resistive silencing of the station body + acoustic enclosure), since the bare station radiates 91dB(A) and silencing lowers it, thus station silencing;
4) Raise the downstream pressure (steady the backpressure at the last stage), since low pressure makes noise and raising eases it, thus raising pressure;
5) Monitor the noise (sound-level meter, alarm >85dB(A)), since gradual growth approaches the limit and early detection catches it, thus monitoring noise;
6) Run an acoustic test (measure Lw), since the lack of testing left the noise undetected and the test reveals the level, thus testing sound;
7) Control the pressure to steady the flow (limit Δp at each stage), since changing conditions make noise and control steadies it, thus controlling pressure;
8) Write the staging and station silencing into the specification, since the original lack of reduction is the root cause of noise and locking it in closes the loop, thus controlling it in the spec.
GB/T 17213.1-2015 Industrial-process control valves