E44-875 · Throttling Noise and Vibration · Control valve · ★★★
Downstream cavitation number σ=0.3 caused cavitation damage to the valve trim, 89dB(A)
[Mechanism] The downstream pressure drops below the vapor pressure, causing cavitation; the collapse impact damages the valve trim and makes noise.
[Calculation] σ=(p2-pv)/(p1-p2)=0.3<1.0, and the collapse impact >1000MPa erodes through the valve trim.
[Design Omission] No backpressure increase, no σ verification, no cavitation-resistant trim.
1) Raise the backpressure to prevent cavitation damage (raise downstream p2 so σ≥1.3), since the original σ0.3 cavitation eroded through the valve trim, thus raising pressure prevents damage;
2) Verify σ (margin ≥1.3), since low pressure causes damage and verification avoids it, thus verifying σ;
3) Replace with cavitation-resistant trim (tungsten carbide valve trim), since the original trim was eroded through by the collapse impact and the replacement resists it, thus replacing the trim;
4) Use multi-stage reduction (3 stages), since concentration causes damage and splitting eases it, thus staging;
5) Monitor the damage (borescope inspection of the trim, alarm on pit depth >0.5mm), since gradual damage approaches breakthrough and early detection catches it, thus monitoring damage;
6) Run a cavitation test (measure the erosion rate under pressure drop), since the lack of testing left the damage undetected and the test reveals the threshold, thus testing cavitation;
7) Control and split the pressure drop (single stage Δp≤0.3MPa), since concentration causes damage and splitting eases it, thus controlling the drop;
8) Write the backpressure increase and σ verification into the calculation sheet, since the original lack of increase is the root cause of damage and locking it in closes the loop, thus controlling it in the calculation.
GB/T 17213.1-2015 Industrial-process control valves