E44-877 · Throttling Noise and Vibration · Reduced-diameter pipe · ★★
A sudden reduction tripled the downstream velocity, giving 88dB(A)
[Mechanism] A sudden pipe contraction makes the velocity rise sharply and the local turbulence noise surge.
[Calculation] After the contraction v=Q/A rises 3 times, and Lw∝v⁸ raises the noise by about 28dB.
[Design Omission] No gradual reduction, no silencing, no pressure increase.
1) Reduce noise with a gradual reduction (a taper instead of a sudden contraction, taper 1:7), since the original sudden contraction tripled v at 88dB(A), thus the gradual change cuts noise;
2) Verify the outlet velocity (≤8m/s), since exceeding it makes noise and verification controls it, thus verifying velocity;
3) Add a silencer (resistive, insertion loss ≥10dB), since the bare pipe radiates 88dB(A) and silencing lowers it, thus silencing;
4) Raise the downstream pressure (steady the backpressure after the contraction to cut turbulence), since low pressure makes noise and raising eases it, thus raising pressure;
5) Monitor the noise (sound-level meter, alarm >85dB(A)), since gradual growth approaches the limit and early detection catches it, thus monitoring noise;
6) Run an acoustic test (measure Lw), since the lack of testing left the noise undetected and the test reveals the level, thus testing sound;
7) Control the pressure drop to steady it (limit Δp), since changing conditions make noise and control steadies it, thus controlling the drop;
8) Write the gradual reduction and silencing into the specification, since the original lack of gradual change is the root cause of noise and locking it in closes the loop, thus controlling it in the spec.
GB/T 3767-2016 Determination of sound power levels of noise sources using sound pressure