E44-892 · Throttling Noise and Vibration · Valve · ★★
The valve stem oscillated at low frequency with ±4% travel; control was unstable
[Mechanism] The servo gain does not match the load, so the valve stem oscillates at low frequency around the set point.
[Calculation] The open-loop gain exceeds the critical value; the oscillation is a few Hz with ±4% travel fluctuation.
[Design Omission] No tuning, no loop-stability verification, no damping.
1) Tune down the gain (adjust the servo gain for stability), since the original open-loop gain exceeded critical and the stem oscillated ±4%, thus tuning steadies the travel;
2) Verify loop stability (phase margin ≥45°), since oscillation means instability and verification steadies it, thus checking stability;
3) Add damping (hydraulic resistance in the actuator), since oscillation vibrates and damping suppresses it, thus adding damping;
4) Switch to a longer stroke (choose a long-stroke valve to reduce relative fluctuation), since a short stroke oscillates and a longer one eases it, thus changing the stroke;
5) Monitor the jitter state (measure travel fluctuation, alarm >±2%), since growing oscillation leads to loss of control, thus early detection;
6) Run a stability test (step response, measure overshoot), since the lack of testing left the oscillation undetected and the test reveals the margin, thus testing stability;
7) Stabilize the control signal (filter out disturbance), since disturbance oscillates and filtering steadies it, thus controlling the signal;
8) Write the tuning and stability verification into the specification, since the original lack of tuning is the root cause of oscillation and locking it in closes the loop, thus controlling it in the spec.
GB/T 17213.1-2015 Industrial-process control valves