E44-042 · Siphon and Backflow · Workshop Drain Pipe · ★★
The pipe has no water seal, and sewer odor backflows into the workshop, causing odor complaints
[Backflow] With no trap water seal, pressure fluctuation lets odor return upward.
[Contamination] The gas containing H2S enters the workshop.
[Design Omission] No water seal and no isolation, so backflow caused odor.
1) Provide a trap water seal ≥50 mm at the drain outlet, because no water seal allows odor backflow with H2S into the workshop, thereby the water seal isolates;
2) Provide automatic make-up water for the water seal when it dries out, because dry-out loses the seal and odor returns, thereby make-up keeps the seal;
3) Provide isolation measures from the sewer, because a direct connection inevitably returns odor, thereby isolating;
4) Run the vent pipe independently outdoors, because independent venting does not create back-pressure or return, thereby venting;
5) Periodically check the water-seal level, because a low level loses the seal, thereby checking the level;
6) Add activated-carbon adsorption at odor points, because adsorption removes H2S, thereby purifying the air;
7) Commission and verify there is no backflow, because verification confirms it, thereby acceptance;
8) Include the water seal in the drainage design, because the original lack of a water seal is the root cause of odor return, thereby the design must include it.
GB/T 50015-2019 Code for Design of Building Water Supply and Drainage