E44-095 · Siphon and Backflow · Cooling Tower Distribution Pipe · ★★
Air trapped in the siphon distribution pipe makes the water distribution uneven, with large cell-to-cell temperature differences and poor cooling
[Air Lock] Air trapped in the siphon pipe unbalances the water distribution.
[Calculation] The air lock makes the flow difference between branches >20%.
[Design Omission] No venting and no pressure balancing, so the water distribution is uneven.
1) Vent the distribution pipe at the high points, because air trapped in the siphon pipe unbalances the branches and venting equalizes them, thereby even water distribution;
2) Use a pressure-balanced distribution design (equal pressure drop across branches), because the air lock creates a pressure difference and balancing equalizes the flows, thereby small cell-to-cell temperature differences;
3) Use a symmetrical layout to reduce bias flow, because asymmetry lowers the far-end pressure and symmetry equalizes it, thereby even distribution;
4) Install flow meters to monitor each branch, because a flow difference >20% needs quantification and monitoring detects it early, thereby adjusting in time;
5) Verify with flow-field simulation, because cooling tower distribution is complex and simulation can predict it, thereby the design controls it;
6) Measure the distribution evenness at commissioning (outlet water temperature difference between cells ≤2℃), because uneven distribution degrades cooling and measurement is needed, thereby acceptance;
7) Locally adjust orifice plates to balance the branches, because some branches remain biased and orifice adjustment compensates, thereby refining it;
8) Include water distribution in the cooling tower design, because the original lack of venting/pressure balancing caused unevenness, thereby providing venting and pressure balancing already at the design stage.
GB/T 7190-2018 Mechanical Draft Cooling Tower