E44-938 · Siphon and Backflow · Metering · ★★
Backflow, metering error, disorder
[Mechanism] Backflow reverses the flow direction in the metering section, distorting the flow meter reading and disrupting the metering.
[Calculation] The backflow is v≈0.8 m/s in the reverse direction, the flow meter's forward reading has a +15% error, and the cumulative total is inaccurate.
[Design Omission] No check valve, no flow-direction check, and no reverse-flow alarm.
1) Install a check valve ahead of the metering pipe (to prevent backflow entering the section), because backflow reverses the flow direction and the check valve cuts off the source and preserves the forward direction, thereby maintaining the metering flow direction;
2) Change the flow meter to bidirectional metering with a reverse-flow alarm (alarm on reverse flow), because backflow first shows as reverse flow and is cut off early, thereby monitoring the flow direction to prevent inaccuracy;
3) Check the elevation difference so the metering side is always 0.3 m above the backflow side, because a positive difference eliminates the reverse driving force and the layout prevents backflow, thereby stabilizing the flow direction;
4) Provide fast shutoff in the metering section (pneumatic ≤2 s) interlocked on reverse flow, because an erroneous opening reverses the flow and fast shutoff limits the volume, thereby controlling the volume and reducing the error;
5) Perform a backflow test (open the valve and verify the metering does not reverse), because the design omitted the difference check and the test confirms the isolation effect, thereby verifying the isolation;
6) Control the operating difference ≥0.3 m with an alarm (adjust if lower), because a stable difference prevents backflow and controlling it prevents reversal, thereby preventing inaccuracy in operation;
7) Calibrate the flow meter periodically with actual flow (error ≤0.5%), because backflow degrades accuracy and calibration restores it, thereby keeping the metering accurate;
8) Write the check valve and flow-direction checking into the metering regulations, because the root cause of inaccuracy is backflow-induced reversal, so the regulations must govern to prevent disorder.
GB/T 20801.3-2020 Design code for industrial metallic piping