Knowledge Base › Electrical Sensor Error Case › Choosing Too Low a Temperature Accuracy Class Doubles the Steady-State Error

Choosing Too Low a Temperature Accuracy Class Doubles the Steady-State Error

E45-003 · Sensor Selection and Range · Temperature sensor PT100 Class B · ★★

Problem Description

Temperature control required ±0.1 ℃ but a Class B PT100 (tolerance ±0.3 ℃) was actually used; the steady-state error was ±0.25 ℃, 2.5 times out of tolerance, and product performance scattered

Root Cause

[Mechanism] A Class B PT100 has a tolerance of ±(0.3+0.005|t|) ℃; at 100 ℃ that is ±0.8 ℃, far larger than the required ±0.1 ℃.
[Calculation] The sensor error + transmitter error + lead-wire error add up to a total system error of ±0.25 ℃, 2.5 times out of tolerance.
[Design Omission] The sensor class was not selected at control accuracy × 1/3 and three-wire compensating leads were not used; the accuracy class is too low.

Corrective Solution

① Class matching: control accuracy ±0.1 ℃ → select a Class A PT100 (±0.15 ℃) or 1/3 DIN (±0.1 ℃) so the sensor error is held within 1/3 of the control accuracy
② Transmitter: pair a high-accuracy transmitter with error ≤0.05%FS and calibrate at four points → reduce the total system error from ±0.25 ℃ to ≤0.12 ℃
③ Wiring scheme: change to three-wire or four-wire to compensate lead resistance → eliminate the extra ±0.5 ℃ error that two-wire brings as temperature varies
④ Lead control: shorten the sensor lead to <10 m and shield it → suppress long-line thermal drift and interference that add error, and stabilize the signal
⑤ Algorithmic compensation: add feedforward compensation to the control loop → absorb the sensor's inherent error and reduce steady-state offset
⑥ Accuracy alarm: warn when the deviation >0.15 ℃ → correct in time before the out-of-tolerance condition scatters product quality
⑦ Standard-source calibration: recalibrate on site with a 0 ℃ ice point/100 ℃ boiling water → cancel factory-calibration drift
⑧ Lock in selection: write the accuracy class × 1/3 selection rule into the temperature measurement datasheet → eliminate class mismatch and out-of-tolerance at the source

Checklist

Reference

GB/T 30121-2013 Industrial platinum resistance thermometers

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »