E45-004 · Sensor Selection and Range · Electromagnetic flowmeter DN50 · ★★★
An electromagnetic flowmeter measured pulp with an 8% gas volume fraction; bubbles clinging to the electrodes made conduction intermittent and the reading sat at zero 30% of the time, badly corrupting the metering
[Mechanism] An electromagnetic flowmeter requires a full pipe and high conductivity; an 8% gas content forms a gas-liquid two-phase flow that momentarily opens the electrode circuit and loses the signal.
[Calculation] Bubbles clinging to the electrodes sharply raise the contact resistance, making the output low by more than 50% and intermittently zero.
[Design Omission] The media gas fraction was not evaluated and no Coriolis mass flowmeter suitable for two-phase flow was selected; the principle is mismatched.
① Principle matching: media gas content 8% → switch to a Coriolis mass flowmeter to measure mass flow, which is unaffected by gas content and meters continuously and accurately
② Full-pipe assurance: install an air vent at the high point of the pipe to keep it full → eliminate the fatal electromagnetic flaw of a reading stuck at zero 30% of the time when the pipe is not full
③ Reduce gas content: degas upstream to bring the gas content <2% → return to the measurable range of the electromagnetic type (threshold 3%)
④ Electrode selection: choose cleanable or scraper-type electrodes → periodically remove clinging bubbles and avoid a sharp rise in contact resistance
⑤ Empty-pipe alarm: stop when the signal is lost >5 s → discard invalid data that counted toward output despite readings stuck at zero 30% of the time
⑥ Signal filtering: add low-signal cutoff and filtering → suppress the jumping of intermittent signals and stabilize the reading
⑦ Live calibration: during commissioning, cross-check by the weighing method → verify with real flow how the design value deviates from the actual gas-content effect
⑧ Lock in selection: write the media gas-fraction evaluation into the flowmeter selection table → eliminate principle mismatch and inaccuracy at the source
GB/T 18659-2018 Electromagnetic flowmeters for closed conduits