E45-020 · Installation Position and Orientation · Type-K Thermocouple on a Heating Furnace · ★
The junction box is 50mm from the furnace wall at an ambient temperature of 60℃, and the compensated reading is 12℃ lower than the actual value
[Mechanism] A high cold-junction temperature reduces the thermoelectric emf; if that high temperature is not compensated, the reading is low.
[Calculation] Cold junction t_c = 60℃, requiring compensation E(60℃) = 2.4mV (type K); without it ΔT approaches the 60℃ order, and the measured value is 12℃ low.
[Design Omission] The cold junction was not moved away, no compensating cable with stable temperature was used, and the cold-junction temperature was not measured.
① Move the cold junction away: move the junction box at least 300mm from the furnace wall (was 50mm) → keeps the cold junction near room temperature and compensates for the missing 60℃ high-temperature correction
② Compensating cable: switch to a compensating cable at stable temperature (compensate at room temperature) → copper cable does not compensate the cold junction and adds error; the reading becomes accurate
③ Cold-junction transmitter: install a cold-junction temperature transmitter for real-time compensation → the ambient drifts; compensate dynamically
④ Heat shield: fit a heat shield on the junction box to lower the ambient temperature → radiative heat is strong; steady the cold junction
⑤ Reference comparison: compare periodically with a reference thermocouple (difference <1℃) → drift is gradual; calibrate in time
⑥ Longer sheath: choose an armored extended sheath to move the cold junction outward → furnace heat conducts along the stem; separate it from the source
⑦ Temperature-rise verification: run a 25/60℃ cold-junction temperature-rise test to verify compensation → design often skips it; confirm by measurement
⑧ Make it stick: write the cold-junction keep-away requirement into the thermocouple installation card → eliminates low readings from proximity to heat at the source
GB/T 16839 Thermocouples