E45-023 · Installation Position and Orientation · Pressure Transmitter on a Sewage Line · ★★
The horizontal dead end of the pressure tap accumulates 30mm of sludge; the reading drifts up 0.01MPa and then freezes unchanged
[Mechanism] The medium does not flow in the dead end, so suspended solids settle and block the pressure transfer channel, distorting the pressure transfer.
[Calculation] Dead-end volume V = πd²L/4; sludge deposits at about 1mm/month, so in 3 months the pressure channel plugs and the reading freezes.
[Design Omission] The tap was not sloped downward, no flushing ring was provided, and no anti-clog type was chosen.
① Downward slope: re-slope the pressure tap to at least 1:10 downward (from horizontal) → the horizontal run let sludge build up and block the transfer; it now drains itself and does not accumulate
② Flushing ring: fit a flushing ring and purge the dead end on a shift basis → sludge deposits gradually; flush it clean
③ Diaphragm type: switch to a flanged diaphragm transmitter mounted flush to the wall → remote-sensing taps clog; measure directly
④ Tap location: place the tap in a flowing section, away from stagnation zones → medium in a dead end does not flow and easily deposits; tap the flowing section
⑤ Local comparison: compare periodically with a local gauge (difference <1%) → clogging is gradual and drifts the reading up; correct it early
⑥ Freeze protection: insulate the impulse line against freezing (sewage freezes easily) → freeze expansion plugs the line; keep it clear
⑦ Pressure test: apply 0/0.2MPa to confirm the channel is clear → design often skips it; confirm by measurement
⑧ Make it stick: write the downward slope and flushing into the tap drawing → eliminates horizontal dead-end sludge at the source
GB/T 1226 Pressure gauges