E45-080 · Signal Interference and EMC · PLC Analog Input · ★★
The AI channel noise is ±0.4% (it was ≤0.1%) and control is unstable
[Mechanism] An unshielded signal cable picks up radiated noise in the electromagnetic environment, which enters the PLC AI directly and produces high noise.
[Calculation] An unshielded cable next to a VFD picks up Vn≈20mV; against the 10V AI range that is 0.2%, and with several harmonics superimposed the effective noise reaches ±0.4%.
[Design Omission] Ordinary parallel cable was used, with no conduit and no shielding.
① Switch to shielded cable: replace the parallel signal cable with shielded twisted pair → noise drops 15dB
② Metal conduit: run the cable the whole way in metal conduit → shielding effectiveness ≥60dB
③ Single-end grounding: ground the shield at a single point at the receiving end → avoids ground loops
④ Filtering: add software averaging (16 samples) and a hardware low-pass filter at the AI input → noise drops to ±0.1%
⑤ Keep away from the source: route the cable ≥300mm from the VFD → less picked-up noise
⑥ Module isolation: add isolation to the AI module → blocks common mode
⑦ Verification by test: AI noise in the actual electromagnetic environment (≤0.1%) → confirm
⑧ Institutionalize: write the analog cable type into the IO list → gatekeeping at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields