MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Electrical Sensor Error Case › Single-End Shield Grounding Increases Noise

Single-End Shield Grounding Increases Noise

E45-081 · Signal Interference and EMC · 4-20mA Temperature Transmitter · ★★

Problem Description

After the shield was changed to single-end grounding the noise increased to ±0.6℃ (it was ±0.2℃ with both ends grounded)

Root Cause

[Mechanism] Under high-frequency interference, grounding the shield at only one end leaves the shield body at high impedance to ground, so the shield acts as an antenna that picks up high frequencies and, with no termination, converts common mode into differential mode.
[Calculation] With shield ground resistance Rg=10Ω, interference f=10MHz and shield inductive reactance X_L=2πfL (L≈1μH)≈63Ω, single-end grounding makes the shield discontinuous, raises the transfer impedance Zt and increases coupling.
[Design Omission] Single-end grounding was applied by mistake (it is valid only at low frequency and still requires 360° termination).

Corrective Solution

① 360° termination: bond the shield to the enclosure through metal connectors at both ends with a 360° ring → continuous shielding, high-frequency shielding ≥60dB
② Distinguish by frequency: single-end grounding is acceptable at <1MHz, but high frequencies must be 360° terminated at both ends → choose by frequency band
③ Equipotential bonding: bond the cabinets at both ends (resistance ≤0.1Ω) → no ground-potential difference
④ Common-mode choke: add a common-mode choke at the high-frequency end → suppresses common mode
⑤ Re-evaluation: measure the noise of both grounding schemes and keep the lower one → data-driven decision
⑥ High-coverage shield: switch to a shield with braid coverage ≥85% → stronger shielding
⑦ Verification by test: look at the high-frequency noise in the spectrum (20dB lower) → confirm
⑧ Institutionalize: write the shield-grounding rule into the EMC card → gatekeeping at the source

Checklist

Reference

GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL