E45-082 · Signal Interference and EMC · Inductive Proximity Switch · ★★
When an adjacent relay pulls in, the proximity switch outputs falsely (3~5 times per minute) and workpieces are missed
[Mechanism] Opening and closing of the relay contacts produces an arc spark that radiates a broadband electromagnetic pulse; coupled into the proximity switch's oscillator circuit it makes the switch misjudge metal as nearby.
[Calculation] The contact arc voltage is about 300V with a bandwidth up to tens of MHz, and at 0.5m the field strength E≈several V/m exceeds the proximity switch's immunity threshold, causing false triggering.
[Design Omission] The relay had no RC snubber, the proximity-switch cable was not shielded, and the two were not kept apart.
① RC snubber: place an RC network (100Ω+0.1μF) across the relay coil and a varistor across the contacts → arc suppression and 20dB less radiation
② Shielded cable: change the proximity-switch cable to shielded twisted pair → suppresses radiation
③ Keep apart: maintain ≥200mm from the relay → lower field strength
④ Hardware debounce: add debouncing at the switch signal input (10ms) → filters false pulses
⑤ Shielded box: mount the relay in a metal shielded box → reduces radiation at the source
⑥ Supply bead: add a ferrite bead to the relay supply → blocks conducted noise
⑦ Verification by test: false triggers during relay operation (0 times) → confirm
⑧ Institutionalize: write the relay EMI treatment into the card → gatekeeping at the source
GB/T 17626.3-2016 Radiated radio-frequency electromagnetic field immunity test