E45-083 · Signal Interference and EMC · Hopper Scale · ★★
The moment a large motor starts, the weighing reading jumps by ±0.5kg (it was stable within ±0.02kg) for 0.5s
[Mechanism] The inrush current of motor starting creates a transient magnetic field and a supply-voltage dip, which couple through the common ground into the weighing amplifier and make the reading jump.
[Calculation] The starting current is about 5× rated (100A) with a large di/dt, inducing a transient e≈0.5V in the signal loop; superimposed, it causes a ±0.5kg jump that lasts until starting completes.
[Design Omission] The weighing system shared a supply with the motor, with no isolation and no delayed sampling.
① Supply separation: feed the weighing system from a separate branch (independent isolated supply) → cuts the common source
② Isolated amplification: isolate the front end (≥1.5kV) → blocks common mode
③ Delayed sampling: wait 500ms after motor start before sampling → avoids the transient
④ Filtering and peak clipping: add a hardware low-pass filter plus software median filtering → clips spikes
⑤ Independent grounding: ground the weighing system at a single point → reduces common-ground noise
⑥ Twisted-pair shielding: use shielded twisted pair for the signal cable → suppresses induction
⑦ Verification by test: reading under starting conditions (jump ≤±0.05kg) → confirm
⑧ Institutionalize: write the separation of weighing and power circuits into the card → gatekeeping at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields