E45-084 · Signal Interference and EMC · Thermocouple · ★★
After the induction furnace starts, the thermocouple reads 15℃ high (it was stable within ±1℃) and returns to normal as soon as the furnace stops
[Mechanism] Leakage flux from the induction-heating coil induces eddy currents and an EMF in the thermocouple wires and junction, introducing a spurious thermal EMF that makes the temperature read high.
[Calculation] With coil leakage flux B≈2mT, frequency 20kHz and signal-loop area A=3cm², the induced e=2πfBA≈7.5mV, equivalent to +15℃.
[Design Omission] The thermocouple wires were not shielded, not kept away from the coil, not twisted, and not filtered.
① Twisted-pair shielding: change the thermocouple wires to shielded twisted pair with 360° termination → loop area approaches zero and induction drops 90%
② Keep away from the coil: stay ≥1m from the induction coil or route through an iron conduit → the magnetic field attenuates
③ Ferromagnetic shielding: sleeve with an iron or permalloy tube → magnetic shielding ≥20dB
④ Low-pass filtering: add a low-pass filter (cutoff 10Hz) → suppresses high frequencies
⑤ Cold-junction compensation: use precision cold-junction compensation → true temperature
⑥ Signal isolation: add isolation → blocks common mode
⑦ Verification by test: compare against a standard thermocouple with the furnace running (difference ≤1℃) → confirm
⑧ Institutionalize: write keeping temperature-measurement lines away from induction sources into the card → gatekeeping at the source
GB/T 17626.3-2016 Radiated radio-frequency electromagnetic field immunity test