E45-085 · Signal Interference and EMC · Multi-Channel Temperature Sensors · ★★
Three sensors are grounded at different points, so their readings crosstalk and the differential-pressure display deviates by ±0.4℃ and varies with the load
[Mechanism] Sensors grounded at multiple points develop ground-potential differences through their differing ground resistances; this differential voltage adds to the signal as common-mode crosstalk, so the channels interfere with one another and the readings fluctuate with load.
[Calculation] With ground resistances r1=2Ω and r2=8Ω and loop current I=1A, the ground-potential difference ΔU=I·(r2−r1)=6V; through unbalanced amplification it appears as ±0.4℃ of crosstalk.
[Design Omission] Multiple sensors were grounded at multiple points; there was no star single-point grounding and no isolation.
① Single-point grounding: bring all sensor signal grounds together at one star point → removes the ground-potential difference and drives crosstalk to zero
② Signal isolation: add isolated amplification to each channel (isolation ≥1kV) → breaks the common-mode path
③ Equipotential bonding: bond the cabinets to each other (resistance ≤0.1Ω) → no potential difference
④ Differential input: switch to differential acquisition to suppress common mode → CMRR≥100dB
⑤ Independent supply: give each sensor its own isolated supply → reduces common-source noise
⑥ Shielding: ground the signal-cable shield at one end → blocks electric fields
⑦ Verification by test: compare the channels under load switching (difference ≤0.1℃) → confirm
⑧ Institutionalize: write the grounding topology into the EMC card → gatekeeping at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields