E45-089 · Signal Interference and EMC · 4-20mA Display Meter · ★★
After sharing a ground conductor with the welding machine the meter pinned at full scale (above 20mA) and once burned out its input module
[Mechanism] The welding machine's heavy current through the shared ground raises the ground potential, which couples into the meter input, overvoltages it to full scale, and can even burn out the module.
[Calculation] With welding current I=100A and shared-ground resistance R=0.05Ω, the ground potential rises by ΔU=I·R=5V, exceeding the meter's isolation margin and puncturing the input.
[Design Omission] The meter shared a ground with the welder, with no isolation and no overvoltage protection.
① Separate grounding: use separate grounds for the meter and the welder (≥3m apart) → removes the common-ground potential rise
② Signal isolation: add an isolation barrier at the input (isolation ≥1.5kV) → breaks the common-mode path
③ Overvoltage protection: add a TVS at the input (clamp 30V) → prevents puncture
④ Independent supply: power the meter from an isolated supply → reduces common-source coupling
⑤ Equipotential bonding: bond the cabinet for equipotentiality while isolating the signal → safe
⑥ Shielding: ground the signal-cable shield at one end → blocks electric fields
⑦ Verification by test: meter under welding conditions (full-scale deflection gone, no burn-out) → confirm
⑧ Institutionalize: write the separated grounding into the EMC card → gatekeeping
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields