E45-104 · Signal Interference and EMC · Shielded Signal Cable · ★★
After both ends of the shield are grounded, the high-frequency noise actually increases (by +10dB versus single-ended)
[Mechanism] Grounding the shield at multiple points forms a ground loop; the ground potential difference drives a current in the shield, turning it into an antenna that radiates/picks up high frequency.
[Calculation] With a ΔU=2V between the two grounds, shield inductive reactance X_L=2πfL (f=10MHz, L=1μH≈63Ω) and loop current I=ΔU/X_L≈32mA, the shield becomes an antenna and noise increases by 10dB.
[Design Omission] The shield was connected to different grounds at each end, not bonded equipotentially, and not terminated 360°.
① Single-point grounding: change the high-frequency-signal shield to single-point grounding (or a 360° equipotential termination) → breaks the ground loop, noise down 10dB
② Equipotential bonding: bond the cabinets at both ends (≤0.1Ω) → no potential difference
③ 360° termination: bond the shield with a metal connector ring → continuous shield
④ Isolation: add isolation to the signal → cuts common mode
⑤ High-frequency filtering: add a common-mode choke → suppresses high frequency
⑥ Re-evaluate: measure multi-point vs single-point noise and pick the lower one → decide with data
⑦ Verify by measurement: check the high-frequency noise on the spectrum (down 10dB) → confirmed
⑧ Institutionalize: write the shield-grounding method into the EMC standard → gate at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields